The HPM family is a modular UPS designed to offer the highest possible availability. The power of a single UPS unit can be increased up to 1200 kW and the system can include up to 8 units in parallel. This modular 3 phase UPS also provides one of the highest efficiency ratings in its class and delivers better power protection and quality to the load.The hot-swappable function can reduce the maintenance time to 5 minutes and improves system availability. It provides you higher power density, smaller footprint, and easy-scaling.
General Features
● 138-485 Vac wide input voltage range to minimize battery use
● High input power factor up to 0.99
● 3-level topology design, efficiency is up to 96.5%
● Support parallel expanded operation:maximum is 8 units
● Smart sleeping mode for energy saving and prolong the life time of the system
● User-friendly 7-inch and 10-inch LCD touch screen for easy UPS operation
Technical Specification
Module Model
HPM3300E-RM-50
Cabinet Model
HPM3300E-200
HPM3300E-300
HPM3300E-400
HPM3300E-500
HPM3300E-600
HPM3300E-800
HPM3300E-1000
Cabinet capacity (VA)
200k
300k
400k
500k
600k
800k
1000k
Module capacity (VA)
50k
Max. number
4
6
8
10
12
16
20
INPUT
Nominal voltage
380/400/415Vac, (3Ph+N+PE)
Operating voltage range
138~305Vac for 40% Load; 305~485Vac for 100% Load;
Operating frequency range
40Hz-70Hz
Power factor
≥0.99
Harmonic distortion (THDi)
≤3% (100% linear load)
Bypass voltage range
Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%)
Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Bypass frequency tracking range
±10%
Power Walk In
Support
Generator input
Support
OUTPUT
Rated voltage
380/400/415Vac, (3Ph+N+PE)
Power factor
1
Voltage regulation
±1%
Output
Line mode
Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz)
frequency
Bat. mode
(50/60±0.1%)Hz
Crest factor
3 :1
Harmonic distortion (THDv)
≤2% with linear load; ≤4% with nonlinear load
Efficiency
up to 96.5%
BATTERY
Battery voltage
VRLA battery
360Vdc~600Vdc (30~50pcs continuously adjustable, 30pcs default, 36~50pcs no powerderating; 32~35pcs output power factor 0.9; 30/31pcs output power factor 0.8)
Lithium battery
512Vdc
Power module charge current
20A (Max.)
SYSTEM FEATURES
Transfer time
Utility to Battery : 0ms; Utility to bypass: 0ms
Overload
Line mode
≤110%, 60min; ≤125%, 10min; ≤150%,1min to bypass; >150%, shut down immediately
Bypass mode
30℃: 135% overload for long term; 40℃: 125% overload for long term; >1000% overload for 100 ms
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage
Alarm and Switch off
Self-diagnostics
Upon Power On and Software Control
Backfeed protection
Support
EPO (optional)
Shut down UPS immediately (turn to bypass optional)
Battery
Advanced Battery Management
Noise suppression
Complies with EN62040-3
Audible & visual alarms
Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display
Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
Reading on the LCD display
Input, Output, Battery, Command, Setting, Maintenance
Communication interface
RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
ENVIRONMENTAL
Operating temperature
0℃~40℃
Storage temperature
-25℃~55℃
Humidity range
0~95% (non condensing)
Altitude
<1500m, derating required when >1500m
Noise level
<65dB
<66dB
<68dB
<70dB
<73dB
PHYSICAL
Dimension
UPS cabinet (S)
600×850×2000
600×850×2000
1200×850×2000
2000×850×2000
UPS cabinet (F)
1200×850×2000
Power module
440×620×130
UPS cabinet
270
290
310/470
650
720
980
1080
Net weight (kg)
Power module
34
STANDARDS
Safety
IEC/EN62040-1, IEC/EN62477-1
EMC
IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8)
Module Model
HPM3300E-RM-60
Cabinet Model
HPM3300E-300
HPM3300E-480
HPM3300E-600
HPM3300E-840
HPM3300E-1080
HPM3300E-1200
Cabinet capacity (VA)
300k
480k
600k
840k
1080k
1200k
Module capacity (VA)
60K
Max. number
5
8
10
14
18
20
INPUT
Nominal voltage
380/400/415Vac, (3Ph+N+PE)
Operating voltage range
138~305Vac for 40% Load; 305~485Vac for 100% Load;
Operating freque
40Hz-70Hz
Power factor
≥0.99
Harmonic distortion (THDi)
≤3% (100% linear load)
Bypass voltage range
Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%)
Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Bypass frequency tracking range
±10%
Power Walk In
Support
Generator input
Support
OUTPUT
Rated voltage
380/400/415Vac, (3Ph+N+PE)
Power factor
1
Voltage regulation
±1%
Output
Line mode
Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz)
frequency
Bat. mode
(50/60±0.1%)Hz
Crest factor
3 : 1
Harmonic distortion (THDv)
≤2% with linear load; ≤4% with nonlinear load
Efficiency
up to 96.5%
BATTERY
Battery voltage
VRLA battery
360Vdc~600Vdc (30~50pcs continuously adjustable, 30pcs default, 36~50pcs no powerderating; 32~35pcs output power factor 0.9; 30/31pcs output power factor 0.8)
Lithium battery
512Vdc
Power module charge current
20A (Max.)
SYSTEM FEATURES
Transfer time
Utility to Battery : 0ms; Utility to bypass: 0ms
Overload
Line mode
≤110%, 60min; ≤125%, 10min; ≤150%,1min to bypass; >150%, shut down immediately
Bypass mode
30℃: 135% overload for long term; 40℃: 125% overload for long term; >1000% overload for 100 ms
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage
Alarm and Switch off
Self-diagnostics
Upon Power On and Software Control
Backfeed protection
Support
EPO (optional)
Shut down UPS immediately (turn to bypass optional)
Battery
Advanced Battery Management
Noise suppression
Complies with EN62040-3
Audible & visual alarms
Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display
Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
Reading on the LCD display
Input, Output, Battery, Command, Setting, Maintenance
Communication
RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
ENVIRONMENTAL
Operating temperature
0℃~40℃
Storage temperature
-25℃~55℃
Humidity range
0~95% (non condensing)
Altitude
<1500m, derating required when >1500m
Noise level
<66dB
<70dB
<73dB
PHYSICAL
Dimension
UPS cabinet (S)
600×850×2000
1200×850×2000
2000×850×2000
2000×850×2000
UPS cabinet (F)
Power module
440×620×130
UPS cabinet
290
650
720
980
1080
1200
Net weight (kg)
Power module
34
STANDARDS
Safety
IEC/EN62040-1, IEC/EN62477-1
EMC
IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8)