Dubai Silicon Oasis, Dubai
Brand
KstarQuantity
Kstar‘s next-generation rack cooling system is compatible with the 19-inch cabinet, enabling accurate air supply and a better cooling effect. It is a flexible tool that can be used wherever you want and maintain safe temperatures for servers, routers, hubs, UPS systems and other equipment in rack environments Kstar In-Rack Cooling.pdf
Kstar‘s next-generation rack cooling system is compatible with the 19-inch cabinet, enabling accurate air supply and a better cooling effect. It is a flexible tool that can be used wherever you want and maintain safe temperatures for servers, routers, hubs, UPS systems and other equipment in rack environments
Kstar In-Rack Cooling.pdf
General Features
● Flexibiltiy and compatibility of space:Compatible with different cabinet,rack- mounted installation.
● Accurate airflow:Unique airflow distribution, it forms cold aisle at front .”V”shape evaporator have large surface for air, low air resistance, and it makes cooling more high-efficient.
● Accurate air volume control:Standard stepless regulation EC fan, optimal airflow distribution, power saving fan.
● High efficient dynamic output:DC inverter compressor, it can be adjusted according to the thermal load in real time.
● High efficient EC fan, it can adjust the air volume according to the thermal load in real time.
● High return air temperature design, high sensible cooling and high power efficiency.
● Stepless regulation outdoor unit, smooth running, power-comsumption,low noise, high reliability.
● Professional low load dehumidification design, it can control the humidity and temperature in the cabinet when the thermal
load is very low.
● Standard configuration of electronic expansion valve with strong adaptability, allows better energy saving effect in winter.
● Environmental friendly R410A refrigerant.
Technical Specification
DX Unit
FS***
unit
20
25
40
Configuration
–
Constant temperature
Constant temperature and humidity
Constant temperature
Constant temperature and humidity
Contant temperature
Constant temperature and humidity
Total cooling1)
Kw
3.5
3.5
7.0
7.0
12.5
12.5
Sensible cooling1)
Kw
3.5
3.5
7
7
12.5
12.5
Volume
m³/h
700
700
1350
1350
2300
2300
Sensible heat ratio (SHR)
%
100
100
100
100
100
100
Heating power
Kw
1.0
1.0
2.5
2.5
5.0
5.0
Humidifier capacity
kg/h
–
0.5
–
0.6
–
1
Number of compressor
PCS
1
1
1
1
1
1
Type of compressor(Standard)
/
DC inverter
DC inverter
DC inverter
DC inverter
DC inverter
DC inverter
Voltage
V
220/230
220/230
220/230
220/230
220/230
220/230
Frequency
Hz
50/60
50/60
50/60
50/60
50/60
50/60
Phase
P
1
1
1
1
1
1
Full load
A
17.2
17.4
28.2
28.6
50.2
50.8
Unit weight
kg
27
30
36
39
55
58
Unit width
mm
440
440
440
440
440
440
Unit depth
mm
800
800
800
800
800
800
Unit height
mm
222
222
310
310
444
444
U
5
5
7
7
10
10
Outdoor unit
KCS***
Unit
5
10
18
Voltage
V
220 / 230
220 / 230
220 / 230
Frequency
Hz
50 / 60
50 / 60
50 / 60
Phase
P
1
1
1
Full load
A
0.5
0.7
1.4
Unit weight
kg
38
48
60
Unit width
mm
898
935
981
Unit depth
mm
340
422
458
Unit height
mm
606
807
1256