Dubai Silicon Oasis, Dubai
Brand
KstarQuantity
UIC series UPS is a three phase in and one phase out online transformer-based UPS, maily used in finance system, telecom system, electric power system, working station to meet the high quality and high reliability requirement of the system to power supply.
General Features
● True online double conversion design
● Build-in input and output transformer with strong galvanic isolation
● Wide input range, avoid frequently transfer to battery mode, prolong the battery lifetime
● Intelligent battery management technology, fully protect battery
● Battery cold start function
● Comprehensive and reliable protection
● User-friendly network management
Technical Specification
MODEL
UIC60L
UIC80L
UIC100L
UIC150L
UIC200L
UIC300L
UIC400L
Capacity
(VA/Watts)
6kVA/4.8kW
8kVA/6.4kW
10kVA/8kW
15kVA/12kW
20kVA/16kW
30kVA/24kW
40kVA/32kW
INPUT
Operating
voltage
range
380Vac(±20%), (3Ph+N+PE)
Operating
frequency
range
50/60Hz(±5%)
Power Factor
>0.97 (with filter)
Max. input
current (A)
14
18
23
34
45
68
90
OUTPUT
Output Voltage
220Vac(±0.5%) / 230Vac(±0.5%)
Output
frequency
50/60Hz(±0.5%)
Efficiency
6~8KVA: 85% online 10~40KVA: 90% online
Harmonic
Distortion
(THDv)
<1.5% with linear load
Crest factor
3:1 (max)
BATTERY
Battery voltage
192Vdc
240Vdc
SYSTEM FEATURES
Transfer time
0ms (Line mode →Battery mode)
Overload
≤125% /1min, ≤150% /200ms,to Bypass
LED display
Battery low, Mains status, Inverter, Bypass, UPS failure, Overload
LCD display
I/O voltage, Frequency, Battery voltage, Load percentage,Internal temperature
Communication
interface
RS232, SNMP (optional), Dry contact(optional),RS485
ENVIRONMENT
Operating
Temperature
0℃~40℃
Storage
temperature
-25~55℃
Humidity range
0~95% (non-condensing)
Altitude
<1500m
Noise level
<55dB
PHYSICAL
Dimension
W×D×H (mm)
305×585×864
430×830×1100
Net Weight
(S/H) (kg)
100
110
120
145
155
255
280
STANDARDS
Safety
IEC/EN62040-1; IEC/EN60950-1
EMC
IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4;IEC61000-4-5;IEC61000-4-6;IEC61000-4-8