Dubai Silicon Oasis, Dubai
Brand
KstarQuantity
With the function of constant temperature and humidity, StationAir series precision air conditioners are designed with large air volume and high sensible heat ratio to meet the needs of professional computer room; The design that operation for 365 day* 24 hours non-stop efficient matches cooling system with a large area of evaporator to ensure all-weather optimal energy-saving operation. Application: Small-medium data center, Equipment room, laboratory, storage room.
With the function of constant temperature and humidity, StationAir series precision air conditioners are designed with large air volume and high sensible heat ratio to meet the needs of professional computer room; The design that operation for 365 day* 24 hours non-stop efficient matches cooling system with a large area of evaporator to ensure all-weather optimal energy-saving operation.
Application: Small-medium data center, Equipment room, laboratory, storage room.
General Features
● Total cooling capacity: 5kW~20kW
● High power-efficiency design, EER of standard machine is above 3.0; EER of High power-efficiency machine is above 3.5
● Supply upflow, downflow, upper-front flow, lower-front flow
● R410 environment-friendly refrigerant
● Stepless speed regulating outdoor fan system solve low frequency noise problem
● Electronic expansion valve is standard equipment, and this make it more adaptive for environment
● Patent fan design can reduce 30% energy. The fan supports sinking deployment and non-sinking deployment
● RS485, 5-meters copper pipe, refrigerant and bracket of outdoor unit are standard equipment for cooling capacity below 12.5KW
Technical Specification
DX Unit
ST***
unit
5
7
Unit Configuration
–
Single Cooling
Constant
Temperature
Constant
Temperature
and Humidity
Single Cooling
Constant
Temperature
Contant
Temperature
and Humidity
Total Cooling
Capavity
kW
5.5
7.5
Sensible Cooling
Capavity
kW
5.2
6.8
Air volume
m³/h
2000
2250
Sensible heat ratio
/
0.95
0.91
Heating capacity
KW
3
3
3
3
Humidyfying
capacity
kg/h
2.5
2.5
Number of
compressors
Pcs
1
1
Number of Fans
Pcs
1
1
Voltage
V
220~240
220~240
380~415
220~240
220~240
380~415
Frequency
Hz
50
50
Phase
P
1
1
3
1
1
3
Full-load Current
A
11.6
23.2
15.5
15.3
26.9
19.2
Unit Weight
kg
105
110
120
115
120
130
Unit Width
mm
550
550
Unit Depth
mm
450
450
Unit Height
mm
1750
1750
DX Unit
ST***
unit
12
17
20
Unit Configuration
–
Single Cooling
Constant
Temperature
Constant
Temperature
and Humidity
Constant
Temperature
Constant
Temperature
and Humidity
Total Cooling
Capavity
kW
12.5
17.5
20.5
Sensible Cooling
Capavity
kW
11.3
15.8
18.6
Air volume
m³/h
2850
5000
6200
Sensible heat ratio
/
0.9
0.9
0.91
Heating capacity
KW
4
4
6
6
Humidyfying capacity
kg/h
4
4.5
4.5
Number of compressors
Pcs
1
1
1
Number of Fans
Pcs
1
1
1
Voltage
V
380~415
380~415
380~415
Frequency
Hz
50
50
50
Phase
P
3
3
3
Full-load Current
A
11.3
16.5
16.5
23.7
24.7
Unit Weight
kg
165
170
180
280
300
Unit Width
mm
650
750
750
Unit Depth
mm
550
700
700
Unit Height
mm
1850
1900
1900
Supporting Outdoor unit
KCS***
unit
7
10
18
24
28
Heat
Exchange
Capability
kw
7.6
10.4
18.1
23.8
27.2
Voltage
V
220
220
220
220
220
Frequency
Hz
50
50
50
50
50
Phase
Pcs
1
1
1
1
1
Full-load
Current
A
0.5
0.7
1.4
2.7
2.7
Noise
dB(A)
38.5
43.9
43.6
54.9
52.9
Unit Weight
kg
38
48
60
117
124
Unit Width
mm
877
967
1014
1600
1400
Unit Depth
mm
340
398
375
975
975
Unit Height
mm
608
807
1244
650
650
Foot stool
Height
mm
455
455
Note:
●parameter table.
Air-cooled unit data based on 24°C,50%RH indoor return airtemperature.
The noise data is sound pressure level value of 10m free field.
●ST005,ST007 and ST012 is prefilled refrigerant,and supplied with 5m connecting copper pipe and mounting brackets of
outdoor unit.
●Specifications are subject to change without prior notice.