Dubai Silicon Oasis, Dubai
Brand
KstarQuantity
Embedded with isoltated transformer, UID industrial UPS solution raging from 10kva-120kva are designed for harsh environment especially industrial application.With high power factor up to 0.97. The full DSP control and online double conversion design can offer high levels of reliability and protection for industrial facilities and mission critical systems, nsuring maximum power reliability.
General Features
● Online double conversion
● Full DSP control
● High power factor:0.9
● Wide input adaptability:(380Va/400Vac/415Vac) (-25%/+20%)
● Optimized battery management,self-test&lexible battery configuration
● N+X parallel redundancy
● Strong overload capability:110%/125%/150% overload for 60/10/1min.
● Power walk in
● Generator mode
● LBS synchronization
● Multi-protection
● User-friendly network management
Technical Specification
MODEL
UID/EP10-L
EP20-L
EP30-L
EP40-L
EP60-L
EP80-L
EP100-L
EP120-L
Capacity
(VA/Watts)
10kVA / 8kW
20kVA / 16kW
30kVA / 24kW
40kVA / 32kW
60kVA /48kW
80kVA/ 64kW
100kVA/ 80kW
120kVA/ 96kW
INPUT
Operating
voltage
range
380/400/415Vac (-25% / +20% ), (3Ph+N+PE)
Operating
frequency
range
50/60Hz(±5%)
Power Factor
>0.97 (with filter)
OUTPUT
Output Voltage
380/400/415Vac (±1%)
Output frequency
50/60Hz (±0.05%)
Harmonic
Distortion
(THDv)
<3% with linear load
Crest factor
3:1 (max)
Efficiency
≥90.5%
≥91.5%
BYPASS
Rated voltage
380/400/415Vac
Rated frequency
50/60Hz(auto-sensing)
Voltage
protection
range
Upper limit: +20% (+10%,+15%,+20% adjustable)
Lower limit: -40% (-10%, -20%, -30%, -40% adjustable)
Frequency
protection
range
±10% (±2.5%, ±5%,±10%, ±20% adjustable)
BATTERY
Battery voltage
384Vdc ( 360~384Vdc )
SYSTEM FEATURES
Transfer time
0ms (Line mode →Battery mode)
Overload
≤110%/60min ,≤125%/10min ,≤150%/1min,to Bypass
LED display
Input, Inverter, Bypass, Battery, Output, Status
LCD display
I/O voltage, frequency, power, power factor, battery voltage, current, battery status,
load percentage, UPS status, history record
Communication
interface
Dry contact, RS232, RS485, SNMP card (Optional)
Optional
Harmonic filter, SNMP adapter, LBS cables, battery temperature sensor,Bypass current-sharing inductor
ENVIRONMENT
Operating
Temperature
0℃~40℃
Storage
temperature
-25~55℃
Humidity range
0~95% (non-condensing)
Altitude
<1500m
Noise level
<58dB
<65dB
PHYSICAL
Dimension
W×D×H (mm)
350×650×1050
430×830×1100
720×675×1400
890×775×1600
Net weight (kg)
148
163
230
255
386
426
625
685
STANDARDS
Safety
IEC/EN 62040-1;IEC/EN 60950-1
Performance
IEC 62040-3
EMC
IEC/EN 62040-2;IEC 61000-2-2;IEC 61000-4-2;IEC 61000-4-3;IEC 61000-4-4; IEC 61000-4-5;IEC 61000-4-6;IEC 61000-4-8;IEC 61000-4-11;