With a 7-inch colour touch screen, hot-swappable design, HPM3300E modular UPS features high efficiency (95.8%), high power density, easy scaling, scaling on demand, Parallel redundancy function and occupies only a small amount of floor area and provides safe, reliable, and clear environmentally friendly power to loads. The series' N+X module and built-in system redundancy maintain a steady, reliable source of energy. It can provide the highest level of power protection and has been widely used in various industries such as IT rooms, data centers, banking, healthcare, insurance, and telecommunications.

With a 7-inch colour touch screen, hot-swappable design, HPM3300E modular UPS features high efficiency (95.8%), high power density, easy scaling, scaling on demand, Parallel redundancy function and occupies only a small amount of floor area and provides safe, reliable, and clear environmentally friendly power to loads.

The series’ N+X module and built-in system redundancy maintain a steady, reliable source of energy. It can provide the highest level of power protection and  has been widely used in various industries such as IT rooms, data centers, banking, healthcare, insurance, and telecommunications.

General Features

● Modular design, including power module, bypass module, monitoring module, which means it can be easily integrated in MDC or customized cabinet.

● Flexible power module: 10/15/20/25/30kVA ((2U))

● High input power factor, it is up to 0.99.

● Width input voltage range:line voltage range is 138-485V, UPS would be derating when input voltage is below 305V.

● Parallel redundant configurations:failure of one module will not impact system or site operation.

● Three level topology design, efficiency is up to 95.8%.

● Sleeping Mode to save energy.

● Support parallel expanded operation: maximum is 6 units, Support sharing batteries for the UPS in parallel.

General Features

Module Model

HPM3300E-RM-10

Cabinet Model

HPM3300E-20

HPM3300E-40

HPM3300E-60

Cabinet capacity (VA)

10k~20k

10k~40k

10k~60k

Module capacity (VA)

10k

Max. Number

2

4

6

Module Model

HPM3300E-RM-15

Cabinet Model

HPM3300E-30

HPM3300E-60

HPM3300E-90

Cabinet capacity (VA)

15k~30k

15k~60k

15k~90k

Module capacity (VA)

15k

Max. Number

2

4

6

Module Model

HPM3300E-RM-20

Cabinet Model

HPM3300E-40

HPM3300E-80

HPM3300E-120

Cabinet capacity (VA)

20k~40k

20k~80k

20k~120k

Module capacity (VA)

20k

Max. Number

2

4

6

Module Model

HPM3300E-RM-25

Cabinet Model

HPM3300E-50

HPM3300E-100

HPM3300E-150

Cabinet capacity (VA)

25k~50k

25k~100k

25k~150k

Module capacity (VA)

25k

Max. Number

2

4

6

Module Model

HPM3300E-RM-30

Cabinet Model

HPM3300E-60

HPM3300E-120

HPM3300E-150

Cabinet capacity (VA)

30k~60k

30k~120k

30k~150k

Module capacity (VA)

30k

Max. Number

2

4

5+1

INPUT

Nominal voltage

380/400/415Vac, (3Ph+N+PE)

Operating voltage range

138~305Vac for 40% Load; 305~485Vac for 100% Load;

Operating frequency range

40Hz-70Hz

Power factor

≥0.99

Harmonic distortion (THDi)

≤3% (100% linear load)

Bypass voltage range

Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%)

Min. voltage: -45% (optional-10%, -15%, -20%, -30%)

Bypass frequency range

Frequency protection range: ±10%

Power Walk In

Support

Generator input

Support

OUTPUT

Rated voltage

380/400/415Vac, (3Ph+N+PE)

Power factor

1.0

Voltage regulation

±1%

Output frequency

Line Mode

Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz)

Bat. Mode

(50/60±0.1%)Hz

Crest factor

3:1

Harmonic distortion (THDv)

≤1% with linear load; ≤3% with nonlinear load

Efficiency

up to 95.8%

BATTERY

Battery voltage

Optional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional);

360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8)

Power module charge current

18A (Max.)

SYSTEM FEATURES

Transfer time

Utility to Battery : 0ms; Utility to bypass: 0ms

Overload

Line Mode

≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately.

Bypass Mode

135% overload for long term; >1000% overload for 100 ms

Overheat

Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately

Low battery voltage

Alarm and Switch off

Self-diagnostics

Upon Power On and Software Control

Backfeed

Support

EPO

Shut down UPS immediately (turn to bypass optional)

Battery

Advanced Battery Management

Noise suppression

Complies with EN62040-3

Audible & Visual alarms

Line Failure, Battery Low, Overload, System Fault

Status LED & LCD display

Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault

Reading on the LCD display

Input, Output, Battery, Command, Setting, Maintenance

Communication interface

RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)

ENVIRONMENTAL

Operating temperature

0℃~40℃

Storage temperature

-25℃~55℃

Humidity range

0~95% (non condensing)

Altitude

<1500m, derating required when >1500m

Noise level(from 1M distance)

<58dB

<60dB

<62dB

PHYSICAL

Dimension              W×D×H (mm)

UPS cabinet

485×850×353(8U)

485×850×575(13U)

485×850×752(17U)

Power module

440×620×86(2U)

Net weight (kg)

UPS cabinet

69

79

98

Power module

10kVA: 19; 15~30kVA: 21

STANDARDS

Safety

IEC/EN62040-1, IEC/EN62477-1

EMC

IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8)

Specifications are subject to change without prior notice.

Brands we stock
cisco.svg
asus.png
fortinet.png
dell.png
idXrlLpGCL_logos.png
HPE_Main_Logo.png
hikvision.png
cisco.svg
asus.png
fortinet.png
dell.png
idXrlLpGCL_logos.png
HPE_Main_Logo.png
hikvision.png
cisco.svg
asus.png
fortinet.png
dell.png
idXrlLpGCL_logos.png
HPE_Main_Logo.png
hikvision.png
Compare
Products
Your compare is curently empty
Compare Products
Modular UPS-HPM Family (10-150kVA) | Buy in Dubai, UAE | Codeeotech